Serviceline Industrial Sensors
Serviceline Explosion Protection

Inductive sensor NCN3-F25F-N4-Y41364

NCN3-F25F-N4-Y41364
  • For installation in housing
  • Direct mounting on standard actuators
  • ATEX & IECEX certifications


NAMUR sensors must be operated with approved switch amplifiers. Please find suitable devices below:

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  NCN3-F25F-N4-Y41364

General specifications
Switching function2 x normally closed (NC)
Output typeNAMUR
Rated operating distance3 mm
Installationflush mountable
Assured operating distance0 ... 2.43 mm
Actual operating distance2.7 ... 3.3 mm typ.
Reduction factor rAl 0.52
Reduction factor rCu 0.43
Reduction factor r304 0.86
Reduction factor rSt37 1
Reduction factor rBrass 0.54
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 kΩ)
Switching frequency0 ... 1500 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected≥ 3 mA
Measuring plate detected≤ 1 mA
Time delay before availability≤ 1 ms
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd1038 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007
EN 60947-5-2/A1:2012
IEC 60947-5-2:2007
IEC 60947-5-2 AMD 1:2012
Approvals and certificates
IECEx approval
Equipment protection level GaIECEx TUN 17.0021X
Equipment protection level GbIECEx TUN 17.0021X
Equipment protection level DaIECEx TUN 17.0021X
Equipment protection level MbIECEx TUN 17.0021X
ATEX approval
Equipment protection level GaTÜV 99 ATEX 1479 X
Equipment protection level GbTÜV 99 ATEX 1479 X
Equipment protection level DaTÜV 99 ATEX 1479 X
UL approvalcULus Listed, General Purpose
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0456
CCC approval
Hazardous Location2020322315002262
NEPSI approval
NEPSI certificateGYJ19.1410X
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typeMINI-COMBICON
Housing materialPBT
Sensing facePBT
Degree of protectionIP67 (Sensor side)
IP20 (Connection side)
Mass37 g
Tightening torque, fastening screwsM5 x 25 : 2.7 Nm
Dimensions
Height20 mm
Width52 mm
Length45 mm
NotePlease use Phönix FK-MCP 1,5/4-ST-3,81 connector
General information
Use in the hazardous areasee instruction manuals

Classifications

SystemClasscode
ECLASS 13.027273901
ECLASS 12.027273901
ECLASS 11.027220501
ECLASS 10.0.127220501
ECLASS 9.027220501
ECLASS 8.027220501
ECLASS 5.127220501
ETIM 9.0EC002714
ETIM 8.0EC002714
ETIM 7.0EC002714
ETIM 6.0EC002714
ETIM 5.0EC002714
UNSPSC 12.139121550

Details: NCN3-F25F-N4-Y41364

Documents: NCN3-F25F-N4-Y41364

Instruction manualsFile TypeFile Size
ИнструкцииPDF194 KB
Návod k poużitíPDF186 KB
Instruktions manualPDF184 KB
Instruction manualPDF185 KB
KasutusjuhendPDF178 KB
KäyttöohjePDF178 KB
Manuel d'instructionsPDF189 KB
BetriebsanleitungPDF187 KB
Οδηγίες χρήσηςPDF197 KB
HandleidingPDF186 KB
Instruction manual / BetriebsanleitungPDF184 KB
Használati útmutatóPDF189 KB
Manuale di istruzioniPDF187 KB
Lietošanas pamācībaPDF185 KB
Instrukciju vadovasPDF187 KB
Instrukcja obsługiPDF187 KB
Manual de instruçõesPDF189 KB
Manual de utilizarePDF189 KB
Návod na poużitiePDF188 KB
Navodila za uporaboPDF183 KB
Manual de instruccionesPDF188 KB
ManualPDF183 KB

CAD+CAE: NCN3-F25F-N4-Y41364

CADFile TypeFile Size
CAD 3-D / CAD 3-DSTP285 KB
CAD Portal / CAD PortalLINK---

Associated Products: NCN3-F25F-N4-Y41364

Accessories
fa
fa
fa
fa

Our amplify article gives interesting insights about the development of the new, modern portfolio of inductive proximity sensors from Pepperl+Fuchs. Get the whole story here! 

 

 

Knowledge Base for Inductive Sensors

The knowledge base for inductive sensors contains extensive expertise and supports you in the highly precise and smooth operation of the sensors in your machinery and plants.

VariKont with Active Shielding Technology

The VariKont inductive sensors with Active Shielding Technology ensure high switching distances, no matter the installation situation and the surrounding material. Benefit from easier equipment design and reduced costs!

Inductive Safety Sensors SIL 2 PL d

As the SIL 2/PL d inductive safety sensors have no dead band, data transfer can occur with no minimum distance between sensor and target. Discover the optimized portfolio for demanding environments.